Gap analysis
We assess the building against WELL, LEED or RESET requirements and set out a roadmap.
Certification
Certification needs reliable air quality data. We plan the monitoring, install suitable monitors and support the documentation from pre-certification to renewal.

WELL, LEED, RESET Air and Dubai’s Al Sa’fat system all reward buildings that prove good indoor air with data. Continuous monitors logging PM2.5, CO₂ and TVOC provide that proof, and the same data shows what to fix before an assessor visits.
Standards
The main air quality targets in each framework, side by side.
| Parameter | WELL v2 (A01) | RESET Air v2.1 | Dubai Municipality |
|---|---|---|---|
| PM2.5 | ≤ 15 µg/m³ | < 35 µg/m³ (high performance < 12) | 35 µg/m³ (24 h) |
| PM10 | ≤ 50 µg/m³ | — | 150 µg/m³ (24 h) |
| CO₂ | — | < 1,000 ppm (high performance < 600) | 800 ppm (8 h) |
| TVOC | ≤ 500 µg/m³ (monitoring option) | < 500 µg/m³ (high performance < 400) | 0.6 mg/m³ (8 h) |
| Formaldehyde | ≤ 50 µg/m³ | — | 0.01 ppm (8 h) |
Services
We assess the building against WELL, LEED or RESET requirements and set out a roadmap.
Monitor count, density and placement that meet the standard’s rules.
Pre-assessment monitoring to catch problems before performance testing.
Data exports, reports and coordination with your certification consultant.
Briefings for facility teams and occupants on keeping air quality on target.
Ongoing monitoring and reporting for renewals and upgrades.
FAQ
Have another question? Ask our team
Feature A01 (Air Quality) requires PM2.5 at or below 15 µg/m³ and PM10 at or below 50 µg/m³ in occupiable spaces, formaldehyde at or below 50 µg/m³ (or total VOC monitoring at or below 500 µg/m³), carbon monoxide at or below 9 ppm and ozone at or below 51 ppb.
Continuous monitoring of PM2.5, CO₂, TVOC, temperature and humidity. RESET Air v2.1 sets acceptable daily averages of under 35 µg/m³ PM2.5, under 1,000 ppm CO₂ and under 500 µg/m³ TVOC, with stricter high-performance targets of 12 µg/m³, 600 ppm and 400 µg/m³.
Kaiterra states that its Sensedge Go is RESET Grade B certified and part of the Works with WELL catalog. Atmocube’s datasheet shows the Works with WELL and RESET marks. We confirm the right model and placement for your project.
Yes. Dubai’s Al Sa’fat green building system includes indoor air quality compliance for new buildings (401.06) and existing buildings (401.07), with testing carried out by specialised companies or laboratories using calibrated equipment.
Bring us in early. Monitoring before performance testing avoids surprises.

HawaQ is the indoor air quality division of PRO TECHnology in Dubai. We measure the air in buildings across the UAE and the GCC, then fix what the data shows.